STANDARD BATTERY SCOPE OF WORK (FLOODED/WET)
Annual Maintenance Routine
The annual Maintenance Routine consists of the following:
- Perform digital low resistance ohm meter readings and inspection on all intercell and intertier connections.
- Rehabilitate up to 20% of all connections as required by above test and inspection. All connections requiring rehabilitation over the 20% limit will be billed on a time and material basis.
- Verify proper torque of all bolted connections.
- Clean and neutralize all cells and racks.
- Measure and record all individual specific gravity readings.
- Measure and record all individual cell and string float voltages.
- Individual cell inspection, seals, sediment levels, positive and negative plates, flame arrestors, electrolyte levels.
- Adjust electrolyte levels as required.
- Record temperature of electrolyte of representative pilot cells.
- Verify integrity of the battery rack.
- General cleanliness of the battery and battery room.
- Provide computer analysis and historical archiving of all battery data and furnish an Annual Maintenance Routine Report.
- All distilled water to be supplied by customer or billed to customer.
Contact one of our experienced Sales Professionals for more details; 1-800-452-6832.